Honeywell Home THX9321 Prestige 2.0 Manual page 40

Table of Contents

Advertisement

®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
ISU
Installer Setup
Number
Name
0, 100 to 25,000 sec
3220
Heating Derivative
Off
3240
Minimum
Compressor Off Time
1 - 5 minutes
0, 30, 60, 90 seconds, 2, 3, 4, 5,
3260
Extended Fan Run
6, 7, 8, 9, 10, 11, 12, 13, 14, 15
Time in Cool
minutes
0, 30, 60, 90 seconds, 2, 3, 4, 5,
3260
Extended Fan Run
6, 7, 8, 9, 10, 11, 12, 13, 14, 15
Time in Heat
minutes
2 or 4 periods per day
4000
Number Of Schedule
Periods
Off
4010
Pre-Occupancy
1 hour
Purge Duration
2 hour
3 hour
Standard
4020
Type of Override
Initiate Occupancy
68-0311—08
®
IAQ WITH EIM
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
Default
0 sec
5 minutes
0 seconds
0 seconds
4 periods per
day
Off
Standard
40
Residential,
Commercial
Requires
or Both
EIM
Commercial
No
The default Heating Derivative is 0 seconds
which is appropriate for most applications. Do
not change this setting unless advised to do so
by Resideo technical support.
The derivative makes adjustments to the
algorithm for fast acting systems.
Both
No
The thermostat has a built in compressor
protection (minimum off timer) that prevents
the compressor from restarting too early after a
shutdown. The minimum-off timer is activated
after the compressor turns off.
If there is a call during the minimum-off timer,
the thermostat shows "waiting for equipment"
in the display.
Both
No
After the call for cooling ends, the thermostat
keeps the fan on for the selected amount of
time for increased efficiency. This may re-
introduce humidity into the living space.
Both
No
After the call for heating ends, the thermostat
keeps the fan on for the selected amount of
time for increased efficiency.
Both
No
Residential:
4 Periods = Wake, Leave, Return, Sleep
2 Periods = Wake, Sleep
Commercial:
4 Periods = Occupied 1, Unoccupied 1,
Occupied 2, Unoccupied 2
2 Periods = Occupied 1, Unoccupied 1
Commercial
No
Runs the fan 1 to 3 hours before each occupied
period to provide a comfortable workplace
upon arrival.
Commercial
No
Standard:
The system maintains temperatures
programmed for the occupied and unoccupied
time periods. Pressing OVERRIDE will allow the
user to make a temporary schedule change.
Initiate Occupancy:
The system maintains temperature at an
energy saving level until the Press to Start
Occupancy button is pressed by the user. The
system will then maintain a comfortable
temperature until the occupied period ends.
This option is recommended for cost savings
when the workplace is used infrequently or
arrival times change from day to day (example -
schools). Once the occupancy is activated by
pressing the Press to Start Occupancy button,
the user will still be able to perform a standard
OVERRIDE of the schedule.