ISU
Installer Setup
Number
Name
Thermostat (Internal)
5040
Which Sensors will be
used for
Sensor Name (Remote)
TEMPERATURE
Sensor Name (Remote)
Control? (Multiple
Sensor Name (Remote)
Sensors are
Sensor Name (Remote)
Averaged)
Sensor Name (Remote)
Sensor Name (Remote)
(Up to 6 Remote Sensors)
None
5050
What Terminals are
Wired to the Outdoor
S1
Temperature Sensor?
S2
S3
S4
None
5070
What Terminals are
Wired to the Return
S1
Air Temperature
S2
Sensor?
S3
S4
10K
5080
Return Air
20K
Temperature Sensor
Type
None
5090
What Terminals are
Wired to the
S1
Discharge Air
S2
Temperature Sensor?
S3
S4
10K
5100
Discharge Air
20K
Temperature Sensor
Type
Off
5110
A-Coil Low
Temperature Cutoff
35° F to 65° F (in 5° F increments)
THX9321 PRESTIGE
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
Default
Sensors are
Averaged
(Internal and
Remote)
None
None
10K
None
10K
Off
47
®
2.0 AND THX9421 PRESTIGE
Residential,
Commercial
Requires
or Both
EIM
Both
No
Select the sensors to be used for temperature
control. If you select more than one, the
thermostat will average the temperature
readings from each sensor.
See "Remote Indoor Sensors" beginning on
page 130.
Both
Yes
Wired Sensors requires an EIM (Equipment
Interface Module).
Both
Yes
Wired Sensors requires an EIM (Equipment
Interface Module).
Both
Yes
Wired Sensors requires an EIM (Equipment
Interface Module).
Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
Both
Yes
Wired Sensors requires an EIM (Equipment
Interface Module).
Both
Yes
Wired Sensors requires an EIM (Equipment
Interface Module).
Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
Both
Yes
If an optional Discharge Air Temperature sensor
is used, this feature can help prevent icing on
the air conditioning A-Coil.
When temperature reaches the limit you set,
compressor(s) will shutoff while the system fan
continues to run, until the temperature rises to
a safe level.
®
IAQ WITH EIM
Notes
68-0311—08