THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
ISU
Installer Setup
Number
Name
1 to 6 CPH
3140
Cool / Compressor
Cycles Per Hour -
Stage 1
Note: "Stage 1" is not
displayed if there is
only 1 stage.
1 to 6 CPH
3140
Cool / Compressor
Cycles Per Hour -
Stage 2
1 to 6 CPH
3140
Cool Cycles Per Hour
- Stage 3
1 to 6 CPH
3140
Cool Cycles Per Hour
- Stage 4
68-0311—08
®
IAQ WITH EIM
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
Default
3
3
3
3
36
Residential,
Commercial
Requires
or Both
EIM
Both
No
ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust cycle rate.
This ISU is only displayed when ISU 2070 Cool
/ Compressor Stages is set to 1 stage.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system cycles
less often when load conditions are less than or
greater than a 50% load.
Both
No
ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust cycle rate.
This ISU is only displayed when ISU 2070 Cool
/ Compressor Stages is set to 2 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system cycles
less often when load conditions are less than or
greater than a 50% load.
Commercial
No
ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust cycle rate.
This ISU is only displayed when ISU 1010
Application is set to Commercial and ISU 2070
Cool Stages is set to 3 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system cycles
less often when load conditions are less than or
greater than a 50% load.
Commercial
No
ISU 3010 Temperature Control Options must
be set to Advanced to view or adjust cycle rate.
This ISU is only displayed when ISU 1010
Application is set to Commercial and ISU 2070
Cool Stages is set to 4 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system cycles
less often when load conditions are less than or
greater than a 50% load.