Mechanical installation

Please pay attention to the requirements
that apply to installation.
The frequency converter is
cooled by means of air circulation. For the unit to be
able to release its cooling air, the minimum free
distance above and below the unit must be minimum
100 mm . To protect the unit from overheating, it must
be ensured that the ambient temperature does not rise
above the max. temperature stated for the frequency
converter and that the 24-hour average temperature is
not exceeded. The max. temperature and 24-hour
average can be seen in General technical data.
If the ambient temperature is in the range of 45
°C - 55 °C, derating of the frequency converter
is to be carried out. See Derating for ambient
temperature. Please note that the service life of the
frequency converter will be reduced if no allowance is
made for the derating for ambient temperature.
Integration
All units with enclosure IP 20 must be integrated in
cabinets and panels. IP 20 is not suitable for remote
mounting. In some countries, e.g. in the USA, units with
enclosure NEMA 1 are approved for remote mounting.
Spacing for mechanical installation
All units require a minimum of 100 mm air between
other components and vents of the enclosure.
MG.28.H2.02 -
AKD 2800
Side-by-side
All units can be installed side-by-side and in any position,
as the units to not require ventilation on the side.