Minimum reference, Ref
MIN
Ref
(parameters 204/205).
MAX
FB
-FB
0-20 mA/ 4-20 mA.
MIN
MAX
An output signal is obtained, which is proportional to the
feedback value in the interval Minimum feedback, FB
- Maximum feedback, FB
MAX
0-f
0-20 mA/4-20 mA.
MAX
An output signal is obtained, which is proportional to
the output frequency in the interval 0 - f
202 Output frequency, high limit, f
0 - I
0-20 mA/4-20 mA.
MAX.
An output signal is obtained, which is proportional
to the output current in the interval 0 - I
0 - P
0-20 mA/4-20 mA.
M,N
An output signal is obtained, which is proportional to
the present output power. 20 mA corresponds to the
value set in parameter 102 Motor power, P
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.H2.02 -
- Maximum reference,
MIN
(parameter 414/415).
(parameter
MAX
).
MAX
MAX.
.
M,N
AKD 2800
0 - Temp.
0-20 mA/4-20 mA.
MAX
An output signal is obtained, which is proportional
to the present heatsink temperature. 0/4 mA
corresponds to a heatsink temperature of less than
20 °C, and 20 mA corresponds to 100 °C.