Calculations are taking too long, possibly due
to noise on the motor cables.
ALARM 56: AMT warning during AMT
Alarm/warning limits:
Without brake
AKD 2800
1 / 3 x 200 - 240 V
[VDC]
Undervoltage
215
Voltage warning low
230
Voltage warning high
385
Overvoltage
410
The voltages stated are the intermediate circuit
voltage of the frequency converter with a tolerance
MG.28.H2.02 -
AKD 2800
A frequency converter warning is given while
AMT is being performed.
WARNING 99: Locked
See parameter 18.
With brake
Without brake
1 / 3 x 200 - 240 V
3 x 380 - 480 V
[VDC]
[VDC]
215
410
230
440
400
765
410
820
of ± 5 %. The corresponding line voltage is the
intermediate circuit voltage divided by 1,35.
With brake
3 x 380 - 480 V
[VDC]
410
440
800
820
61