Boiler water temperature control

The switching hysteresis, i.e. the burner runtime, var-
ies subject to the current heat demand.
ERB50 function
Code "04:1"
Depending on the heat demand, values between 6 and
12 K result.
ON
OFF
+9
+3
set
-3
low
average
heat demand
heat demand
Fig. 36
Control sequence
Boiler goes cold
(Set value
2 K)
The burner start signal is set for a set boiler water tem-
perature
2 K and the burner starts its own monitoring
program.
The burner start may be delayed by a few minutes,
depending on the number of auxiliary circuits and the
combustion type.

Cylinder temperature control

Brief description
The cylinder thermostat functions as a constant tem-
perature controller. This is achieved by starting and
stopping the circulation pump for cylinder heating.
The switching differential is
When the DHW cylinder is heated, the default set
boiler water temperature is 20 K above the set DHW
temperature (adjustable via coding address "60" in
group 3 "DHW").
Functions
Priority control
With priority control: (code "A2:2" in group 5 "Heating
circuit"):
During cylinder heating, the set flow temperature is
set to 0
C.
º
The heating circuit pump is switched off.
Without priority control:
The heating circuit pump continues to run.
(cont.)
Time
high
heat demand
2.5 K.
±
ERB80 function
Code "04:2"
Depending on the heat demand, values between 6 and
20 K result.
ON
OFF
+17
+3
set
-3
low
average
heat demand
heat demand
Fig. 37
Boiler heats up
(Set value +2 K)
The burner shuts down.
Frost protection function
If the DHW temperature falls below 5 °C, the DHW cyl-
inder is heated to 20 °C.
Set DHW temperature
The set DHW temperature can be adjusted between
10 and 60 °C.
Function description
Time
high
heat demand
63