Coding 1, Vitotronic 100

Group 1 "General"

Coding
Coding in the factory set condition
System design
00:1
No Function.
Servomotor runtime
40:...
Runtime, valve actuator at plug gSA1.
Factory set condition specified by boiler
coding card.
Participant no.
77:1
LON participant number.

Group 2 "Boiler"

Coding
Coding in the factory set condition
System design
01:1
Single boiler system.
Burner type
02:1
Two-stage burner.
Gas/oil operation
03:0
Gas operation.
Boiler/burner
05:...
Modulating burner:
Burner curve.
Factory set condition specified by boiler
coding card.
120
Vitotronic 100, GC1B / Vitotronic 300-K, MW1B Installation and Service
Possible change
00:0
40:5
to
40:199
77:1
to
77:99
Possible change
01:2
01:3
02:1
02:2
03:1
05:0
05:1
to
05:99
Set automatically if code "01:2" is set.
Boiler control unit is linked into the
cascade.
Runtime adjustable from 5 to 199 sec.
LON participant number,
adjustable from 1 to 99.
Multi boiler system with Vitotronic
300-K control via LON.
Do Not Adjust.
Single stage burner.
Modulating burner.
Oil operation (irreversible).
Linear burner curve.
Non-linear burner curve.
(P
: P
)·100
T
max
P
in kW: Partial output at g of the
T
servomotor runtime
P
in kW: Maximum output
max