Error Description And Error Handling - Kemper KHS Mini Control System MASTER 2.0 Installation And Operating Instructions Manual

Hide thumbs Also See for KHS Mini Control System MASTER 2.0:
Table of Contents

Advertisement

Error description and error handling

Status
Status LED
LED
Backwater in drain
Backwater in drain
Temperature flushing
switched off during
runtime
Volume flushing
switched off during
runtime
PT1000 value too
high
PT1000 value too low
Leak on sensor
Real-time clock data
inconsistent
Flow detected with
valve closed"
"No flow detected
despite open valve"
K410068602008-00 / 09.2018
Error description / Error handling
Status LED
General error
Drain is clogged or cannot accept
the flushing volume.
Float switch on the drain has a
cable break
Medium did not reach the switch-
off temperature in the set time
Set volume not reached
Sensor defective / No sensor
available
Sensor defective / No sensor
available
Pipe failure, moisture on the
sensor
Data in the clock are not
consistent
Flow is detected by the flow
measurement valve when the
valve is closed
No flow is detected during a
flushing process.
69
Status LED
Check the drain
channel, channel
acceptance capacity.
Replace cable / switch
Check the installation
setup and the
maximum flushing
time.
Check the installation
setup and the
Volume operating mode is
maximum flushing
time.
Replace sensor / Check
inputs on the MASTER
operating mode is blocked
Replace sensor / Check
inputs on the MASTER
operating mode is blocked
Check the local area
and remove the
moisture
Check the time & date
and adjust if necessary.
Check battery/replace
if applicable
Check the function of
the flushing valve
Check the flushing line
and the flushing valve
Status LED
Error message!
Defective control will be
completely blocked
Error message!
Defective control will be
completely blocked
Error message!
Temperature operating
mode is blocked in the
defective control.
Error message!
blocked in the defective
control.
Error message!
Temperature flushing
in the defective control.
Error message!
Temperature flushing
in the defective control.
The safety valve is
blocking the system.
All time-based services
are running on incorrect
time/date.
Error message! The
involved valve will be
blocked.
Error message! The
involved valve will be
blocked.