Recommended Torque; Fusing; Ambient Conditions, Ventilation, Mounting Position - Danaher Motion 601...620 Product Manual

Digital servo amplifier
Table of Contents

Advertisement

Danaher Motion
6.2.1

Recommended torque

Connector
X3, X4
X0A, X0B, X7, X8, X9
Ground bolt
6.2.2

Fusing

Internal Fusing
Circuit
Auxiliary supply 24V
Regen resistor
External fusing
Fusible cutouts or similar
(Fuse UL time delay)
AC supply
24V supply
Regen resistor
(
x = S or S-R for 480V applications
6.2.3

Ambient conditions, ventilation, mounting position

Storage, hints
Transport, hints
Supply voltage tolerances
Ambient temperature in operation
Humidity in operation
Site altitude
Pollution level
Vibrations
Noise emission
Enclosure protection
Mounting position
Ventilation
Make sure that there is sufficient forced ventilation within the switchgear cabinet.
®
SERVOSTAR
601...620 Product Manual
F
N1/2/3
F
H1/2/3
F
B1/2
Input power
Aux. power supply
07/2007
Recommended torque
0.5 to 0.6 Nm (4.43 to 5.31 in lb)
0.5 to 0.6 Nm (4.43 to 5.31 in lb)
3.5 Nm (31 in lb)
internal fuse
3.15 AT (FRx-3)
electronic
SERVOSTAR
601/ 603
6 AT (FRx-6)
max. 12 AF (max. FRx-12)
6 AT (FRS-6)
x = N or N-R for 230V applications
ð p.13
ð p.13
min 3x 230V
min 3x 208V
24 VDC (-0% +15%), check voltage drop
0 to +45°C (32 to 113°F) at rated data
+45 to +55°C (113 to 131°F) with power derating
rel. humidity 85%, no condensation
up to 1000m a.m.s.l. without restriction
1000 — 2500m a.m.s.l. with power derating
1.5%/100m
Pollution level 2 to EN60204/EN50178
Class 3111 according to IEC 721-3-3
max. 45 dB(A)
IP 20
generally vertical. ð p.36
forced convection by built-in fan
Technical description
SERVOSTAR
SERVOSTAR
606/ 610
10 AT (FRx-10)
20 AT (FRx-25)
10 AT (FRS-10)
10 AT (FR10-10)
)
AC / max 3x 480V
-10%
AC / max 3x 480V
-10%
614/ 620
+10%
, 50 Hz
+10%
, 60 Hz
2.5% / K
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents