4
1-29 Automatic Motor Adaptation (AMA)
Option:
*
OFF
[0]
[1]
Enable complete AMA
[2]
Enable reduced AMA
Note:
For the best adaptation of the frequency converter, run AMA on a cold motor.
AMA cannot be performed while the motor is running.
AMA cannot be performed on permanent magnet motors.
NB!
It is important to set motor par. 1-2* Motor Data correctly, since these form part of the AMA algorithm. An AMA must be performed
to achieve optimum dynamic motor performance. It may take up to 10 min, depending on the power rating of the motor.
NB!
Avoid generating external torque during AMA.
NB!
If one of the settings in par. 1-2* Motor Data is changed, par. 1-30 to 1-39, the advanced motor parameters, will return to default
setting.
46
Speed down
Set-up select bit 0
Set-up select bit 1
Catch up
Slow down
Pulse input
Ramp bit 0
Ramp bit 1
Mains failure inverse
DigiPot Increase
DigiPot Decrease
DigiPot Clear
Reset Counter A
Reset Counter B
Function:
The AMA function optimizes dynamic motor performance by automatically optimizing the advanced motor pa-
rameters (par. 1-30 to par. 1-35) at motor standstill.
Activate the AMA function by pressing [Hand on] after selecting [1] or [2]. See also the section
Adaptation
. After a normal sequence, the display will read: "Press [OK] to finish AMA". After pressing the [OK]
key the frequency converter is ready for operation.
This parameter cannot be adjusted while the motor is running.
Performs AMA of the stator resistance R
leakage reactance X
and the main reactance X
2
FC 301:
The complete AMA does not include X
from the motor database. Par. 1-35
Main Reactance (X
Performs a reduced AMA of the stator resistance R
between the drive and the motor.
MG.33.AB.02 - VLT is a registered Danfoss trademark
®
VLT
AutomationDrive FC 300 Operating
, the rotor resistance R
, the stator leakage reactance X
S
r
.
h
measurement for FC 301. Instead, the X
h
)
may be adjusted to obtain optimal start performance.
h
in the system only. Select this option if an LC filter is used
s
Instructions
[22]
[23]
[24]
[28]
[29]
[32]
[34]
[35]
[36]
[55]
[56]
[57]
[62]
[65]
Automatic Motor
, the rotor
1
value is determined