5. General Specifications
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Relay 02 (FC 302 only) Terminal number
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
5
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300 V AC 2A
Cable lengths and cross sections for control cables*:
Max. motor cable length, screened
Max. motor cable length, unscreened
Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross section to control terminals
* Power cables, see tables in section "Electrical Data" of the Design Guide
For more information, see section
Control card performance:
Scan interval
Control characteristics:
Resolution of output frequency at 0 - 1000 Hz
Precise start/stop
Repeat accuracy of
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open loop)
Speed control range (closed loop)
Speed accuracy (open loop)
Speed accuracy (closed loop), depending on resolution of feedback device
All control characteristics are based on a 4-pole asynchronous motor
Surroundings:
Enclosure
Vibration test
Max. relative humidity
Aggressive environment (IEC 60068-2-43) H
3)
Ambient temperature
1) Only for ≤ 3.7 kW (200 - 240 V), ≤ 7.5 kW (400 - 480/ 500 V)
2) As enclosure kit for ≤ 3.7 kW (200 - 240 V), ≤ 7.5 kW (400 - 480/ 500 V)
3) Derating for high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
78
1)
(Inductive load @ cosφ 0.4)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
1)
(Inductive load)
1)
on 4-5 (NO) (Resistive load)
2)3)
1)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
1)
on 4-5 (NO) (Resistive load)
1)
on 4-5 (NO) (Inductive load)
1)
on 4-6 (NC) (Resistive load)
1)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
1)
on 4-6 (NC) (Resistive load)
1)
on 4-6 (NC) (Inductive load)
Electrical Data
in the FC 300 Design Guide, MG.33.BX.YY.
(terminals 18, 19)
S test
2
MG.33.AB.02 - VLT is a registered Danfoss trademark
®
VLT
AutomationDrive FC 300 Operating
overvoltage category III/pollution degree 2
FC 301: 50 m / FC 301 (A1-encl.): 25 m/ FC 302: 150 m
FC 301: 75 m / FC 301 (A1-encl.): 50 m/ FC 302: 300 m
1)
IP 20
/ Type 1, IP 21
5% - 93%(IEC 721-3-3; Class 3K3 (non-condensing) during operation
Max. 50 °C (24-hour average maximum 45 °C)
Instructions
240 V AC, 0.2 A
60 V DC, 1A
24 V DC, 0.1A
4-6 (break), 4-5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1A
240 V AC, 2 A
240 V AC, 0.2A
50 V DC, 2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 20 mA
1.5 mm
2
/16 AWG
1 mm
2
/18 AWG
2
0.5 mm
/20 AWG
2
0.25 mm
/ 24 AWG
FC 301: 5 ms / FC 302: 1 ms
+/- 0.003 Hz
≤± 0.1 msec
≤ 2 ms
1:100 of synchronous speed
1:1000 of synchronous speed
30 - 4000 rpm: error ±8 rpm
0 - 6000 rpm: error ±0.15 rpm
2)
/ Type 1, IP 55/ Type 12, IP 66
1.0 g
class Kd
0 °C
- 10 °C