Danfoss VLT AutomationDrive FC 300 Operating Instructions Manual page 45

Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

®
VLT
AutomationDrive FC 300 Operating
Instructions
1-22 Motor Voltage
Range:
*
Size related
[10 - 1000 V]
1-23 Motor Frequency
Option:
*
50 Hz when parameter
[50]
0-03 = international
[60]
60 Hz when parameter
0-03 = US
1-24 Motor Current
Range:
*
Size related
[0.1 - 10000 A]
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range:
*
Size related
[100 - 60,000 RPM]
This parameter cannot be adjusted while the motor is running.
5-12 Terminal 27 Digital Input
Option:
Function:
Enter the nominal motor voltage according to the motor nameplate data. The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Function:
Min - Max motor frequency: 20 - 1000 Hz.
Select the motor frequency value from the motor nameplate data. If a value different from 50 Hz or 60 Hz is
selected, it is necessary to adapt the load independent settings in par. 1-50 to 1-53. For 87 Hz operation with
230/400 V motors, set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
par. 3-03
Maximum Reference
to the 87 Hz application.
Function:
Enter the nominal motor current value from the motor nameplate data. This data is used for calculating motor
torque, motor thermal protection etc.
Function:
Enter the nominal motor speed value from the motor nameplate data. This data is used for calculating automatic
motor compensations.
Function:
Select the function from the available digital input range.
No operation
Reset
Coast inverse
Coast and reset inverse
Quick stop inverse
DC-brake inverse
Stop inverse
Start
Latched start
Reversing
Start reversing
Enable start forward
Enable start reverse
Jog
Preset ref bit 0
Preset ref bit 1
Preset ref bit 2
Freeze reference
Freeze output
Speed up
MG.33.AB.02 - VLT is a registered Danfoss trademark
4. How to Programme
Motor Speed High Limit [RPM)
and
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[16]
[17]
[18]
[19]
[20]
[21]
45