Add Switch Setting (Address Assignment); Under Communication For Single Bms (Battery String Qty. 1 Set); String Qty. ≤6 Set) - Pylontech PowerCube-X1 Operation Manual

Lithium-ion phosphate energy storage system
Hide thumbs Also See for PowerCube-X1:
Table of Contents

Advertisement

3.6.3 ADD Switch Setting (Address Assignment)

ADD Switch BMS is a 6 bit dial switches to manually distribute the
communication address of the battery system. Nether position is OFF,
means "0". Upper position is ON, means "1". 1
address, and the 6
bit dial switch support a 120Ω resistance (Terminal
th
Resistance).
ADD Switch MBMS is a 6 bit dial switches to manually distribute the
communication address of the battery system. Nether position is OFF,
means "0". Upper position is ON, means "1". 1st bit to 4th bit is for
address, the 5th and the 6th bit dial switch support a 120Ω resistance
(Terminal Resistance).

3.6.3.1 Under communication for single BMS (battery string qty. 1 set)

The BMS's first five bits must set in below <BMS's Address Configure Table>. The last BMS's terminal
resistance must set in "1" (X=1);
The address is configured follow ASCII code: ("X" is terminal resistance).
BMS's Address Configure Table:
3.6.3.2 Under CAN Communication Mode between MBMS and BMS (battery string qty. ≤6 set)
The BMS's first five bits must set in below <BMS's Address Configure
Table>. The last BMS's terminal resistance must set in "1" (X=1), and other
BMS's terminal resistance must set in "0".
The address is configured follow ASCII code: ("X" is terminal resistance).
BMS's Address Configure Table:
The MBMS's ADD Switch set with "000011".
The last 2 bits are terminal resistances.
Note: the 1
to 4
bit dial for MBMS refer to 3.6.3.3
st
th
bit to 5
bit is for
st
th
24
Battery
Address Bit
String
1
10000X
2
01000X
3
11000X
4
00100X
5
10100X
6
01100X
7
11100X
8
00010X
Battery
String
9
10
11
12
13
14
15
16