Conversion factors
June 2019
A.2
K-Factor and inverse K-Factor
Equation A-1: Frequency volumetric flow rate K-Factor
and
Equation A-2: Frequency volumetric flow rate inverse K-Factor
where
KFactor = frequency "K-Factor" (pulses/volume**) (Freq1KFactor and Freq2KFactor)
InvKFactor = frequency "Inverse K-Factor" (volume**/pulse) (Freq1InvKFactor and
Freq2InvKFactor)
FreqQ
(Freq1FullScaleVolFlowRate and Freq2FullScaleVolFlowRate)
MaxFreq = maximum frequency (Hz = pulses/time unit*) (Freq1MaxFrequency and
Freq2MaxFrequency)
* TimeUnit = time conversion factor depends on the VolFlowRate Time Unit data point:
•
volume/second = 1 s/s
•
volume/minute = 60 s/m
•
volume/hour = 3600 s/h
•
volume/day = 86400 s/d
** Volume = where the volume is selected via data points:
•
Units System
•
VolUnitUS
—
—
•
VolUnitMetric
—
—
104
KFactor =
InvKFactor =
= frequency full-scale volumetric flow rate (volume**/time unit*)
FullScale
gallons
barrels
cubic meters
liters
Maintenance and Troubleshooting manual
FreqQ
*
FullScale
(MaxFreq)3600siℎr
(MaxFreq)(3600siℎr)
FreqQ
FullScale
P/N 3-9000-769
*
Gas Ultrasonic Flow Meters