Common Operations And Menu Structure; Execution Modes; Operation Sequence - YOKOGAWA mR10000 436101 User Manual

Hide thumbs Also See for mR10000 436101:
Table of Contents

Advertisement

Common Operations and Menu Structure

Execution Modes

Operation Sequence

20
The recorder has three execution modes.
Operation Mode
This mode is used for normal recording operation. The recorder enters this mode when
the power is turned ON.
Setting Mode
This mode is used to set the input range, alarms, chart speed, and other parameters.
These settings can be changed while recording is in progress. However, the input range
of measurement channels and the computing equation, unit, constant, and TLOG setting
of computation channels cannot be changed while computation (/M1 option) is in
progress.
Basic Setting mode
This mode is used to set the basic specifications of the recorder such as the
thermocouple burnout detection function and the alarm output relay operation. This
mode cannot be entered while the recorder is recording or while computation is in
progress on the computation function (/M1 option). Measurement, recording, and alarm
detection cannot be carried out in this mode.
Power ON
Operation mode
Data display screen
Hold down
for 3 s
1
MENU
Data display setup screen
Hold down
This section explains the operations that need to be carried out when using the recorder
for the first time.
• Preparing to Record
Load the chart paper and pens (pen model) or ribbon cassette (dot model). Change
the date/time if necessary.
For the operating procedure, see page 26.
• Setting the Channel Input Range and Other Parameters
Set the measurement conditions suitable for the object being measured.
This manual explains the following operations.
• Setting the input range and alarm (see page 32 for the procedure)
• Changing the chart speed (see page 41 for the procedure)
• Recording/Displaying Data
Start/Stop the recording operation and carry out various types of printouts. Also,
switch the display screen and change the displayed contents.
For the operating procedure, see page 40.
Display "End=Store" and press
Setting mode
for 3 s
MENU
Basic Setting mode
Hold down
+
for 3 s
IM 04P01B01-02E

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents