System Sensor/ M-Ias Multi-Sensor & Laser Detectors - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

ZX Fire Alarm Control Panels
16.6.2 System Sensor/ M-IAS Multi-sensor & Laser detectors
The System Sensor / Morley-IAS Multi-sensor and laser detectors are supported in panel software
version 824 onwards and loop driver software version 9 onwards.
There are 6 modes of operation (alarm levels) available on the multi-sensor and 9 on the laser
detector, as in the tables below.
Threshold
45
Level 1 alarm
55
Level 2 alarm
72
Level 3 alarm
86
Level 4 alarm
101
Level 5 alarm
116
Level 6 alarm
Threshold
47
Level 1 alarm
55
Level 2 alarm
62
Level 3 alarm
69
Level 4 alarm
76
Level 5 alarm
83
Level 6 alarm
90
Level 7 alarm
97
Level 8 alarm
105
Level 9 alarm
Where the control panel sensitivity day mode is used, the multi-sensor/laser mode can be modified
according to the specific site requirements. This allows a different mode of operation at different times
of the day (see 'Sensitivity Mode' in Section 11.3).
When night mode is invoked, the multi-sensor mode is fixed at alarm level 4, with pre-alarm fixed at
alarm level 3. The laser mode is fixed at alarm level 5 and pre-alarm level 4.
To program the day mode operation for each multi-sensor/laser device, select 'edit thresholds' from
the edit device menu. Set the required threshold level for both fire and pre-alarm that corresponds to
the desired mode of operation (refer to tables above).
Note that it is important to adhere strictly to the suggested threshold settings for each
mode – these are chosen to allow for various system / device tolerances.
It is also important that after any Multi-Sensor device replacement, an Auto Learn must be performed.
This has the effect of re-initialising the device (enabling the heat only alarm level)
Commissioning Manual
Mode
1% / ft obscuration.
1% - 2% / ft obscuration (self-adjusting).
2% / ft obscuration.
2% - 3.5% / ft obscuration (self-adjusting).
3.5% / ft obscuration.
Heat only.
System Sensor Multi-sensor Modes of Operation
Mode
0.02% / ft obscuration.
0.03% / ft obscuration.
0.05% / ft obscuration
0.10% / ft obscuration.
0.20% / ft obscuration
0.50% / ft obscuration
1.00% / ft obscuration
1.50% / ft obscuration
2.00% / ft obscuration
System Sensor Laser Modes of Operation