Table 3 - Led Functions - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

ZX Fire Alarm Control Panels
Indicator
FIRE
Fault
Acknowledged
Disablement
Test
Sounder Fault
Delayed Mode
Relays Disabled
Earth Fault
System / CPU Fault
Sounders Disabled
Alarms Silenced
Supply Fault
Power
Zone FIRE
Zone Fault
1
This includes loop-based sounders.
Commissioning Manual
Colour
Red
The panel has detected a fire alarm
condition, or the 'Sound Alarms' key
has been pressed.
Yellow
The panel has detected a fault.
Yellow
A fault or alarm has been
acknowledged and the internal
buzzer silenced.
Yellow
Part of the system, either input or
output, has been disabled manually
by the user.
Yellow
The system is in test mode. Zone
LED indicators show which zones
are being tested.
Yellow
This indicates a wiring fault with one
of the sounder output circuits.
Yellow
This indicates that the system is
operating with delays to the sounder
outputs and the delays are active (in
force).
Yellow
The relay outputs have been
disabled.
Yellow
An earth connection fault has
occurred on a cable.
Yellow
The CPU has reset or a system fault
has occurred.
Yellow
Some or all of the sounder
have been disabled.
Yellow
The sounder
silenced.
Yellow
There is a problem with the power
supply, battery or supply input.
Green
STEADY: Indicates AC Power is
present. FLASHING: Indicates a loss
of AC Power.
Red
FLASHING: The zone is in a fire
alarm condition.
Yellow
FLASHING: The zone contains faulty
devices.
STEADY: The zone is either disabled
or in test mode.
Table 3 – LED Functions
Document No. 996-175-000-1, Revision 01
Function
1
outputs
1
outputs have been
MORLEY-IAS
How to Clear
Identify and correct the condition
causing the alarm and then perform
a panel reset.
Correct the condition causing the
fault and then perform a panel reset.
Correct the condition causing alarm
or fault and then perform a manual
reset. NOTE: If another alarm or fault
occurs, the internal buzzer
automatically resounds.
Re-enable the device or devices.
Refer to Disablement Function.
Cancel test when finished.
Correct the fault condition and then
perform a panel reset.
The delays may be enabled or
disabled. Refer to Disablement
Function.
Refer to Disablement Function.
Correct the fault condition and then
perform a panel reset.
Correct the problem, if appropriate,
and then perform a panel reset.
Refer to Disablement Function.
Correct the alarm condition and then
perform a panel reset. NOTE: Press
SILENCE / RESOUND again to
reactivate the sounders. If a new
alarm occurs, the alarms will
resound.
Correct the fault condition and then
perform a panel reset.
See Supply Fault.
Correct the alarm condition and then
perform a panel reset.
Correct the fault condition and then
perform a panel reset.
Re-enable devices or cancel test
mode.
Page 7