MORLEY-IAS

5.4 Sounders

5.4.1 Sounder Output Types

EN54-2 7.11
EN54
Delays to Outputs.
!

5.4.2 Allocating Sounders

All sounder outputs, on-board, loop-driven and peripheral bus units are programmed in the same way.
The only functional difference between the three types of device is that some loop-driven units
(depending on type and manufacturer) cannot be synchronized. Therefore, it is recommended that
any single installations that require multiple, pulsed sounder circuits should only use the on-board and
the peripheral bus outputs.
Press '7' to select the sounders option from the configure menu. The display will show which ringing
pattern numbers are assigned to which sounders.
Each ringing pattern maps the sounders operation relative to zones in alarm.
Immediately after a 'wipe system', followed by 'auto learn' of both loop driven and
peripheral bus devices, the system defaults to:
All ringing patterns are set to ON for all zones.
Base card sounder A set to pattern number 3
Base card sounder B set to pattern number 4
Base card sounder C set to pattern number 5
Base card sounder D set to pattern number 6
All other loop and peripheral sounders set to pattern number 1
On selecting the sounder option, the display will show the setting for the base card, sounder A, as
follows:
---------------------------------------------
SOUNDER
A flashing cursor over the number field on the display indicates that a new pattern number can be
entered from the keyboard.
To inspect or change the zoned ringing rules associated with the pattern number, press the 'Enter'
key. The display will then show:
---------------------------------------------
Pattern
Page 30
The system supports three different methods of connecting
sounders:
1.
Connected directly to terminals on the base card.
2.
Connected to addressable sounder modules on any of the
signalling loops.
3.
Connected to addressable 4-way sounder cards on the RS485
peripheral loop.
[ Panel in Commissioning mode ]
A
[ Panel in Commissioning mode ]
zone
3
001
to 080
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
(ZX5Se & ZX10Se only)
(ZX5Se & ZX10Se only)
Pattern
003
MODE
ON
Commissioning Manual