MORLEY-IAS
5.4 Sounders
5.4.1 Sounder Output Types
EN54-2 7.11
EN54
Delays to Outputs.
!
5.4.2 Allocating Sounders
•
All sounder outputs, on-board, loop-driven and peripheral bus units are programmed in the same way.
•
The only functional difference between the three types of device is that some loop-driven units
(depending on type and manufacturer) cannot be synchronized. Therefore, it is recommended that
any single installations that require multiple, pulsed sounder circuits should only use the on-board and
the peripheral bus outputs.
•
Press '7' to select the sounders option from the configure menu. The display will show which ringing
pattern numbers are assigned to which sounders.
•
Each ringing pattern maps the sounders operation relative to zones in alarm.
Immediately after a 'wipe system', followed by 'auto learn' of both loop driven and
peripheral bus devices, the system defaults to:
All ringing patterns are set to ON for all zones.
Base card sounder A set to pattern number 3
Base card sounder B set to pattern number 4
Base card sounder C set to pattern number 5
Base card sounder D set to pattern number 6
All other loop and peripheral sounders set to pattern number 1
•
On selecting the sounder option, the display will show the setting for the base card, sounder A, as
follows:
---------------------------------------------
SOUNDER
•
A flashing cursor over the number field on the display indicates that a new pattern number can be
entered from the keyboard.
•
To inspect or change the zoned ringing rules associated with the pattern number, press the 'Enter'
key. The display will then show:
---------------------------------------------
Pattern
Page 30
•
The system supports three different methods of connecting
sounders:
1.
Connected directly to terminals on the base card.
2.
Connected to addressable sounder modules on any of the
signalling loops.
3.
Connected to addressable 4-way sounder cards on the RS485
peripheral loop.
[ Panel in Commissioning mode ]
A
[ Panel in Commissioning mode ]
zone
3
001
to 080
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
(ZX5Se & ZX10Se only)
(ZX5Se & ZX10Se only)
Pattern
003
MODE
ON
Commissioning Manual