Pattern Pulse-On-On; Detector Loop Addressable Sounder Circuit Controller Units (Scc); Peripheral Loop Addressable Sounder Circuit Controller Units - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

MORLEY-IAS
5.4.2.8

Pattern PULSE-ON-ON

---------------------------------------------
Pattern
RESULT: Sounder circuit A will turn on if two or more detectors have gone into fire in zone 1, or two or
more in zone 2 etc. If only one detector is in fire the sounder will pulse.
The configuration shown on the display becomes effective immediately after the 'Enter' or 'Yes' key is
pressed. Pressing the 'No' key will abort the operation and return to the commissioning menu.
The 'Yes' key also automatically advances to the next zones to be defined.
Zone 1 Call Point
in Alarm
Zone 1 Sensor 1
Zone 2 Sensor 1
in Alarm
in Alarm
No Action
No Action
SOUNDERS
SOUNDERS
PULSE
PULSE

5.4.3 Detector Loop Addressable Sounder Circuit Controller Units (SCC)

One or more addressable sounder controller units may be included on each loop of the system. Refer
to the relevant manufacturer's literature for precise details on how to wire these devices.
Open and short circuits on the sounder wiring are detected by the SCC module, logged, and displayed by
the control panel. Wiring faults on the loop are also detected by the panel and again logged and displayed.
Any SCC connected to the system can be configured to sound for fires in ANY zone in the system.
When SCC units are used, their zone programming selection is shown by using the same 'Sounder'
configuration option as the on-board outputs. For example, an SCC module wired onto loop 2 at
address number 117 may be shown as:
---------------------------------------------
This shows all sounders wired into the SCC module located on loop 2 at address 117 will use ringing
pattern number 1.
From Version 828 Onward
When using an Hochiki CHQ-AB beacon device in combination with a CHQ-BS base
sounder (using the same address), both devices may have independent pattern settings.
Settings associated with the CHQ-AB will be displayed with a suffix 'a' appended to the
address e.g. '2:117_a' and CHQ-BS with a suffix 'b' e.g. '2:117_b'.

5.4.4 Peripheral Loop Addressable Sounder Circuit Controller Units

Up to 15 4-way sounder cards can be added to the system via the RS485 peripheral loop.
These sounders are programmed in the same way as the other sounders.
Page 34
[ Panel in Commissioning mode ]
zone
3
001 to 080
Zone 1 Sensor 2
in Alarm
Pattern
Validated
SOUNDERS
ON
[ Panel in Commissioning mode ]
SOUNDER
2:117_a
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
1/2 Sensors
PULSE/ON -> ON 120s
Pattern
001
120 s
SOUNDERS
ON
Commissioning Manual