ZX Fire Alarm Control Panels
NOTE: Only one mode of operation can be selected to be operational at one time.

11.2 Delayed Mode

EN54-2 7.11
EN54
Delays to Outputs
!

11.2.1 Commissioning Delayed Mode

Press '1' to select Delayed mode from the Day Mode Menu. The display will prompt whether the mode
is to be used.
---------------------------------------------
Press 'No' to inhibit the mode and return to the Day Mode menu.
Press 'Yes' to enable the mode. The display will then prompt the start and end times for the day period.
---------------------------------------------
START at
Press 'Yes' to accept and step on. Press 'No' to change and then enter the required start time using
the number buttons.
---------------------------------------------
START at
Press 'Yes' to accept and step on. Press 'No' to change and then enter the required end time using the
number buttons. Note: the delay mode will remain active for the extent of the 'FINISH at' minute.
A two-stage timer is built into the day mode.
After entry of the start / end times, the display prompts the stage timers as follows:
Commissioning Manual
The panel can be configured to operate in a delayed mode
during the daytime in any specified zone.
During this time, high sensor signals will generate a fire
message at the panel, but delay the output to the sounders. The
panel will initiate a full fire alarm if action is not taken on this
warning within a specified time.
Manual call points (Pull Stations) will always generate an
immediate fire alarm, regardless of any day mode setting.
Ensure that at least one sounder circuit is configured for immediate
operation when the fire alarm is confirmed (end of stage 2 time).
Ensure that the fire output relay is configured with the
appropriate pattern so that it does NOT turn on until the fire
alarm is confirmed (end of stage 2 time).
[ Panel in Commissioning mode ]
Allow mode
?
[ Panel in Commissioning mode ]
08:45
?
[ Panel in Commissioning mode ]
08:45
FINISH at 16:35 ?
Document No. 996-175-000-1, Revision 01
MORLEY-IAS
Page 43