Class Change; Table 6 - List Of Device Actions - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

MORLEY-IAS
1. Fault
2.
Zone Fire
3.
Bomb Alert
4.

Class Change

5.
Security
1
6.
Non-latch
7.
Plant
1
8.
Group Disable
1
9.
Confirmed Fire
1
10. Panel Reset
1
11. Evacuate
1
12. Silence Alarms
13. not used
Press the Yes key once the desired option is shown. The display will then revert to the normal device
display, but will in addition show in the bottom right corner the alarm action of the input. For example:
---------------------------------------------
L1 Z056 A106 "PLANT CONTROL ROOM
I/O unit
The display can also be placed in this 'action display' mode at any time by pressing the '6' key when
viewing any device.
5.2.4.7
Class Change
EN54-2
EN54
Class Change
N/A
1
These are local to the panel only and are not broadcast across a network.
Page 24
Closing the input produces a 'warning' message on the display. The common
'Fault' LED and the corresponding zone fault LED will also illuminate.
Closing the input puts the designated zone into fire. 'True' Break Glass Call
Points should ALWAYS be set to this option.
Note: With panel software prior to version 834 this was called 'Fire'.
Creates a 'bomb alert' from the designated zone. All sounders / relay outputs will
react according to their programming for this zone.
Closing the input forces all system sounders to ring. This condition is not
latched. Once the input opens again the sounders will stop ringing.
Allows the input class 'security alert' to be configured.
Allows an input device to create a temporary system event that is cleared when
the input is restored to its normal condition. This option is not normally used on
fire systems. Contact technical support department for further information before
Closing the input produces a 'warning' message on the LCD, but does not
Allows an input device to disable a group of detectors remotely from the panel.
This input acts as an MCP and overrides any programmed delays to operate
This will reset the panel. Performs in the same way as the panel RESET key.
Will operate all configured outputs immediately.
Will de-activate all currently active outputs.
Allows an input device to be turned off. Any action or state change at the input
Table 6 – List of Device Actions
[ Panel in Commissioning mode ]
Signal= 16
The operation of a 'Class Change' input MUST be restricted to
LEVEL 2 ACCESS only. Install accordingly using a key switch to
activate or locate in a restricted area.
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
using this option.
illuminate the yellow fault LED's.
configured outputs.
will be ignored.
Security
"
Commissioning Manual