Time / Date Option; Time/Date; System (Clear Memory) - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

ZX Fire Alarm Control Panels

7 Time / Date Option

Page 2 of the Commission menu is shown below:
---------------------------------------------

1)Time/Date

3)Power Supplies
The Time / Date option allows the various time and date functions to be checked or modified.
Press '1' from page 2 of the commission menus to select the Time and Date option and show the
current date and time. Then press 'CHANGE' and the display then shows a menu of functions
available, as follows:
---------------------------------------------
CHANGE: 1)Time 2)Date 6)System 7)Crystal
Select the required option using the numeric keys.
7.1 Time / Date
These options allow the current date and time to be specified and entered into the panel memory.
To change the time or date select the appropriate option (Time = 1, Date = 2) and enter the correct
values.
The time is in 24-hour format.
On networked systems, the master panel will automatically set the time and date.

7.2 System (Clear Memory)

This option allows the system configuration memory to be cleared. The operation returns all
commissioning data to factory default settings.
To select the option, press '6' and follow the instructions.
WARNING:
This option will completely wipe the configuration memory. All previously entered data
will be lost.
---------------------------------------------
Do you want to Wipe the WHOLE SYSTEM ?!!
Press the ENTER key to start to wipe the system.
Commissioning Manual
[ Panel in Commissioning mode ]
2)Program Integrity
4)Passwords
[ Panel in Commissioning mode ]
[ Panel in Commissioning mode ]
Document No. 996-175-000-1, Revision 01
MORLEY-IAS
[n]
Page 37