8-Way Input Units; Remote Control; Panel Status Outputs; Simulating Control Keys - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

ZX Fire Alarm Control Panels
5.3.4.2

8-Way Input Units

To change the input action on 8-way input boards press '6' to select the 'Action' option. The display
will then show how the first input has been configured:
---------------------------------------------
Input " I1 " creates [ Zone Fire ]
"<>" to scroll inputs, CHANGE or ENTER
Press the '<' or '>' key to scroll through inputs 1 to 8.
Press the CHANGE key to change the action produced by a contact closure occurring at the input to
the unit. The options available are as listed above for signalling loop devices.
Press the ENTER key once all inputs have been set.
Each of the inputs can have a different action. For example, input 1 could put the zone in fire,
input 2 could put the zone in security alert, input 3 could put the zone in bomb alert, etc.
For information on commissioning and expanded / non-expanded mode use of the 8-Way Input Unit, refer
to the documentation supplied with the card.

5.3.5 Remote Control

Remote activation of some front panel control key functions and monitoring of panel status can be
achieved through specific use of peripheral input and relay cards from software version 830 onwards.
5.3.5.1

Panel Status Outputs

A 4-way relay card must be configured to address '19' on the peripheral bus and an auto-learn
performed. Operation of the first three outputs will then be as follows:
5.3.5.2

Simulating Control Keys

An 8-way input card must be configured to address '20' on the peripheral bus and an auto-learn performed.
It is also important that the input card is configured in non-expanded mode with each of the following inputs
configured as 'No Action' – for those inputs requiring control key functionality as follows:
Input Card - Input ref

Table 8 - Peripheral 8-way Input card, remote control operation

Commissioning Manual
[ Panel in Commissioning mode ]
Relay Card Output
1
2
3

Table 7 - Peripheral Relay Unit, remote control operation

1
2
3
4
Document No. 996-175-000-1, Revision 01
'Remote' Operation
Reset (momentary – 4 sec typical)
Muted
Silenced
'Remote' Operation
Reset
Mute/ Accept
Silence
Evacuate
MORLEY-IAS
Page 29