12 Setup Option

Setup options define the way in which the panel is configured, such as the number and type of loop
driver boards fitted. They should be checked when a panel is first installed, but will rarely need altering
after this time.
The options are presented as a series of questions. Press 'Yes' if the setting is as required. The
following table details the options:
Option
Language
Qty of Loop Drivers
Type of Loop Driver
Approvals
1
Standard
Calibration /Check
Time
Device Interrupts
3
AC Fail Timer
Reset Inhibit Time
Silence Inhibit Time
1
Standard panel software will have options for EN54 and BS5839 operation. UL864 operation may be provided for other
worldwide market areas.
2
Hochiki ESP devices rely on interrupts for their basic operation and so this parameter is not displayed when the panel is
configured for Hochiki.
3
Only Available if the panel is configured for UL Operation.
Commissioning Manual
Determines the language displayed on the alphanumeric display.
Options: Language options depend on the software version installed.
If only one language available, this option is not displayed.
Determines the number of loop driver boards installed in the panel.
(ZX2Se = 1 to 2, ZX5Se/ZX10Se = 1 to 5).
Determines the type of loop driver installed. Options: Morley-IAS,
System Sensor, Apollo, Hochiki ESP, Nittan.
NOTE: Isync compatible, loop driver boards self identify and do not need
to be changed manually. The Isync software version installed in the
board is also displayed on the bottom line.
Determines the standard to which the panel software complies. Options:
EN54, BS, UL864.
Determines whether calibration should be performed on the detectors.
Automatic checking of device calibration can be performed at the time
specified. A warning will be given if a device drifts outside its calibration
limits or approaches the pre-alarm threshold. Setting a time of 0:00 will
prevent this check from taking place. Choose a time of day when the
environment can be expected to be in a normal (clean air) condition.
2
Device interrupts provide a way for call point devices to interrupt the
normal polling sequence and so give a fast response. It is possible to
ignore interrupts, if required, by changing this item to FALSE instead of
the default TRUE setting.
This option should normally be set to TRUE unless faultfinding on a
system during the early commissioning phase.
For Apollo, Hochiki and Nittan, this option should be set to TRUE.
For Morley IAS and System Sensor (SSD) devices, this option
should be set to FALSE.
As soon as the ac power is lost, the panel will flash the green power
supply indicator on the front panel.
The panel will not latch a fault condition, until the AC Fail Timer has
elapsed.
The AC Fail Timer can be set in the range 1 – 720 minutes in one-
minute intervals.
3
The reset key can be inhibited for a period after the receipt of a fire
alarm condition at the panel.
The Reset Inhibit Time can be set in the range 0 – 900 seconds in one-
second intervals.
3
The Silence / Resound key can be inhibited for a period after the panel
receives a fire alarm condition.
The Silence Inhibit Time can be set in the range 0 – 900 seconds in one-
second intervals.
This option is only shown if the Reset Inhibit Time is not equal to zero. If
the Reset Inhibit Time is set to zero, this function is made inactive.
Document No. 996-175-000-1, Revision 01
Description
MORLEY-IAS
Default
English
--
--
EN54
0:00
TRUE
1 minute
0 seconds
0 seconds
Page 47