Each zone can have a description assigned to it to identify the area covered by the zone. This
description will appear on the liquid crystal display if any sensor in the zone detects a fault or fire.
---------------------------------------------
Zone 001 is named "SOUTH ANNEXE
The description can be amended by highlighting the location text (using the '>' and '<' keys), pressing
'Change' and entering either, letters, numbers or keywords. This procedure is identical to that used for
editing the sensor location text described in Section 5.2.4.2 below.

5.2.4 Devices

The 'Devices' option from the display gives information on the various types of device fitted on a loop.
Press 2 to select the 'Devices' option. The system will ask which address you want to start at:
---------------------------------------------
Begin inspection at address number
If you would like to start at a different address, then press the 'Change' key and enter your required
address, otherwise say 'Yes' to continue.
The display then gives detailed information about the Device at the chosen address.
Loop Zone Address
--------------------------------------------
L1 Z003 A086 "RESEARCH ROOM 52
Ion Smoke
Device Type
For Apollo protocol loops with Ancillary Sounders attached to applicable sensors, the display then
gives detailed information about the device at the chosen address with an
indicator '+' at the end of the text description of the device (to which the
ancillary sounder is attached). Applicable sensors to which Apollo ancillary
sounders can be connected include ionisation, temperature detectors, etc.
For Morley-IAS and System Sensor protocol loops with ancillary LEDs attached to applicable modules: the
display gives information about the device at the chosen address with an indicator '+' at the end of the text
description of the device (to which the ancillary LED is attached). These ancillary LEDs are, in fact,
configured as if they were relays, meaning that they perform in the same way a
relay does. These outputs, therefore, cannot be pulsed. The ZX Series of fire
control panels can turn on four device LEDs in alarm. The panel can turn on
additional ancillary LEDs, up to the maximum current supported by the loop.
Page 18
[ Panel in Commissioning mode ]
[ Panel in Commissioning mode ]
Location Text
[ Panel in Commissioning mode ]
Signal= 26
Analogue Signal
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
1
Event
"Ev106
(Inputs 2..0=LLH)
Digital input status (Apollo only)
H=Logic High L=Logic Low
"
?
For use with software
version 826 onwards.
For use with software
version 834 onwards.
Commissioning Manual