MORLEY-IAS
11 Day Mode Option
•
Page 3 of the Commission menus is shown below:
---------------------------------------------
1)Day mode
4)Events
1
This option is displayed if the panel is networked to a slave panel.
•
Press '1' to select the 'Day Mode' option from page 3 of the Commission menus.
The DAY MODE option and all sub-menu options require the Memory Lock to be open.
11.1 Day Modes
•
The display then shows three possible day mode options:
---------------------------------------------
1)Delayed mode
3)Verification mode
•
The panel can be commissioned to automatically invoke different operating modes according to the
time of day.
•
Each mode has adjustable start and finishing times. Outside of the designated start and finishing
times, the panel reverts to normal operation. If required, a mode can be set independent of time by
setting the start to '00:00' and finish to '24:00'.
•
The operating modes available are summarized in the table below.
Operating
Mode
Delayed mode
Sensitivity mode
Verification
mode
•
Configure each mode by selecting it from the day mode menu.
Page 42
[ Panel in Commissioning mode ]
2)Setup options
5) Talk To Slave
[ Panel in Commissioning mode ]
2)Sensitivity mode
During the day/night the alarm signal from detectors is immediately recognized and
identified on the panel display, but no outputs turn on until stage1/stage2 timers have
expired. Call points / Pull Stations override this mode.
Allows smoke and temperature detectors to use different pre alarm and fire alarm
thresholds during the day/night.
Allows smoke detectors to tolerate transient alarms according to the programmed
verification delay time during either day or night.
Table 10 – Day Mode Options
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
3)Network [1]
Description
Commissioning Manual