Product Description

ANN-I/O LED Driver Module*

The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40 LEDs
The module is provided with a plastic enclosure for mounting inside the annunciator or accessory
box. The following sections describe hardware installation. Refer to the section titled "ANN-BUS
Options" on page 121 for programming information.
*In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervi-
sory, burglary or trouble signals. Green indicates the presence of power or an activated output.
ANN-I/O Board Layout
Figure 1.8 illustrates the ANN-I/O board showing locations of screw terminals for connection to
the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-BUS ID
number.
32
Standard
Exec 10.5
Table 1.2 PRN-6F Setup Options
Terminals not used (future)
Figure 1.8 ANN-I/O Board Layout
SI.Zero
Auto LF
PAPER
BIN 1
BIN 2
SINGLE
PUSH TRA
PULL TRA
PAP ROLL
ANN-BUS Connector
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Accessories
On
On
12/72"
12/72"
12/72"
12/72"
12/72"
12/72"
ANN-BUS (ID#)
Address DIP
switch