Tab.30
Navigation for BASIC INSTALLER level
Level
Menu cascade
Basic installer
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
Tab.31
Factory settings at BASIC INSTALLER level
Code
Display text
AP016
CH function on
AP017
DHW function on
AP073
Summer Winter
AP074
Force summer
mode
AP083
Enable master
func
AP089
Installer name
AP090
Installer phone
CP510
Temporary Room
Setp
Tab.32
Navigation for INSTALLER level
Level
Menu cascade
Installer
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
7717201 - v03 - 25062019
> Installation Setup > CU-GH08 > Submenu
Description
Enable central heating heat
demand processing
Enable domestic hot water
heat demand processing
Outdoor temperature: upper
limit for heating
The heating is stopped. Hot
water is maintained. Force
Summer Mode
Enable the master functionality
of this device on the S-Bus for
system control
Name of the installer
Telephone number of the
installer
Temporary room setpoint per
zone
> Installation Setup > CU-GH08 > Submenu
Caution
Changing the factory settings may adversely affect the operation
of the boiler.
9.10.3

Control unit settings

Important
All tables show the factory setting for the parameters.
The tables also list parameters that are only applicable if the
boiler is combined with other equipment such as an outdoor
sensor.
All possible options are indicated in the adjustment range. The
display of the boiler only shows the relevant settings for the
appliance.
> Parameters, counters, signals > Parameters
(1)
Range
0 = Off
1 = On
0 = Off
1 = On
10 °C - 30 °C
0 = Off
1 = On
0 = No
1 = Yes
-
-
5 °C - 30 °C
> Parameters, counters, signals > Parameters
(1)
Gas 120
Gas 120
ACE - 65
ACE - 90
1
1
1
1
22
22
0
0
0
0
None
None
0
0
20
20
MID _HMI T-control - Gas 120 ACE
9 Settings
Gas 120
ACE - 115
1
1
22
0
0
None
0
20