5.3

Electrical connections

7717201 - v03 - 25062019
5.3.1

Recommendations

Only qualified professionals may carry out electrical connections, always
with the power off.
Earth the appliance before making any electrical connections.
Power the appliance via a circuit that includes an omni-polar switch with
contact opening distance of 3 mm or more.
When making electrical connections to the mains, respect the polarities.
Danger
Position the various electrical cables in such a way that they never
touch the heating pipes.
Keep the various electrical cables far enough from the heating
pipes so that they cannot be damaged by the effect of the heat.
5.3.2

Electrical power supply

Power supply voltage
Caution
Please ensure the polarities shown on the terminals are followed,
i.e live (L), neutral (N) and earth (
5.3.3

Recommended cable cross section

Decide on the cable according to the following information:
Distance of the appliance from the power source.
Upstream protection.
Neutral operating conditions.
Tab.2
Specifications of the power cable and the power source
Cable cross section
Curve C (circuit breaker)
Differential
230 V AC/50 Hz
)
3 x 1.5 mm²
10 A
30 mA
MID _HMI T-control - Gas 120 ACE