MID _HMI T-control - Gas 120 ACE
5.3.4
1. Unlock the front door.
2. Tilt and lift the door to remove it.
1
MW-2000830-02
3. Remove the two screws and dismantle the rear top panel.
3
MW-2000831-01
4. Unlock and open the cover on the control box.
MW-2000832-01
Caution
Provide a separate power supply for the pump and a power
switch, if necessary.
The output available per outlet is 450 W (2 A, with cos ϕ = 0.7)
and the inrush current must be less that 16 A. If the load exceeds
either of these values, the control must be relayed using a
contactor that must in no circumstances be installed in the control
panel. The sum of the currents from all outlets must not exceed
5 A.