5 Installation
5.5

Gas connection

Fig.13
Connecting the gas pipe
5.6

Air supply/flue gas outlet connections

Fig.14
Connecting the flue gas outlet and
air supply
80/125 mm
100/150 mm
5.7

Electrical connections

24
1. Remove the dust cap from the gas supply pipe
the boiler.
2. Fit the gas supply pipe.
3. Fit a gas tap in this pipe, directly underneath the boiler (within 1
metre).
4. Fit the gas pipe to the gas tap.
Important
The gas tap must always be accessible
1
2
3
4
AD-0000025-02
5.6.1
S Insertion depth 25 mm
1. Connect the flue gas outlet pipe and the air supply pipe to the boiler.
2. Fit the subsequent flue gas outlet pipes and air supply pipes in
accordance with the manufacturer's instructions.
Caution
AD-0000034-01
5.7.1
The table gives important connection values for the control unit.
Tab.18
Supply voltage
Main fuse value F1 (230 VAC)
Fan

Connecting the flue gas outlet and air supply

The pipes must not be resting on the boiler.
Fit the horizontal parts sloping down towards the boiler, with a
gradient of 50 mm per metre.

Control unit

Connection values for control unit
at the bottom of
230 VAC/50 Hz
2.5 AT
230 VAC
7684359 - v.06 - 10012019