9 Settings
Code
Display text
GP022
Tfa Filter Tau
PP014
ChPumpDTRedu
ction
PP016
Max. CH pump
speed
PP017
ChPumpSpeedM
axFactor
PP018
Min CH pump
speed
PP023
Start hysteresis
CH
Tab.36
Parameter
Text display
CP000
MaxZoneTFlowSetpoin
t
CP001
MaxZoneTFlowSetpoin
t
CP010
Tflow setpoint zone
CP011
Tflow setpoint zone
CP020
Zone Function
52
MID _HMI T-control - Gas 120 ACE
Description
Tau factor for average flow
temperature calculation
Reduction of temperature delta
modulating for pump
modulation
Maximum central heating pump
speed (%)
Maximum central heating at
minimum load as percentage of
max pump speed
Minimum central heating pump
speed (%)
Hysteresis to start burner in
heating mode
9.10.4
Maximum Flow Temperature setpoint zone
Adjustment range:
from 7 °C to 90 °C
Maximum Flow Temperature setpoint zone
Adjustment range:
from 7 °C to 90 °C
Zone flow temperature setpoint, used when the zone is set to a fixed flow
setpoint.
Adjustment range:
from 7 °C to 95 °C
Zone flow temperature setpoint, used when the zone is set to a fixed flow
setpoint.
Adjustment range:
from 7 °C to 95 °C
Functionality of the zone
Adjustment range:
0 =Disable
1 =Direct
2 =Mixing Circuit
3 =Swimming pool
4 =High Temperature
5 =Fan Convector
6 =DHW tank
7 =Electrical DHW
8 =Time Program
9 =ProcessHeat
10 =DHW Layered
11 =DHW Internal tank
12 =DHW Commercial Tank
31 =DHW FWS EXT
Range
1 - 255
0 °C - 40 °C
20 % - 100 %
0 % - 100 %
20 % - 100 %
1 °C - 10 °C

List of parametersSCB-02

Description
Gas 120
Gas 120
Gas 120
ACE - 65
ACE - 90
ACE - 115
1
1
18
18
100
100
100
100
30
30
10
10
Factory
setting
90
55
90
50
6
7717201 - v03 - 25062019
1
18
100
100
30
10