Electrical Connection - Samson TROVIS 5432 Mounting And Operating Instructions

Automation system 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5432:
Table of Contents

Advertisement

11

Electrical connection

!
Caution!
For electrical installation, you are required to observe the relevant electrotechnical regula-
tions of the country of use as well as the regulations of the local power suppliers. Make sure
all electrical connections are installed by trained and experienced personnel!
Notes on installing the electrical connections
4
Install the 230 V power supply lines and the signal lines separately! To increase noise im-
munity, observe a minimum distance of 10 cm between the lines. Make sure the minimum
distance is also observed when the lines are installed in a cabinet.
4
The lines for digital signals (bus lines) and analog signals (sensor lines, analog outputs)
must also be installed separately!
4
In plants with a high electromagnetic noise level, we recommend to use shielded cables
for the analog signal lines. Ground the shield at one side, either at the control cabinet in-
let or outlet, using the largest possible cross-section. Connect the central grounding point
and the PE grounding conductor with a cable ≥ 10 mm² using the shortest route.
4
Inductances in the control cabinet, e.g. contactor coils, are to be equipped with suitable
interference suppressors (RC elements).
4
Control cabinet elements with high field strength, e.g. transformers or frequency convert-
ers, should be shielded with separators providing a good ground connection.
Overvoltage protection
4
If signal lines are installed outside buildings or over large distances, make sure appropri-
ate surge or overvoltage protection measures are taken. Such measures are indispens-
able for bus lines!
4
The shield of signal lines installed outside buildings must have current conducting capac-
ity and must be grounded on both sides.
4
Surge diverters must be installed at the control cabinet inlet.
Connecting the controller
The controller is connected as illustrated in the wiring diagram.
Open the housing to connect the cables. To connect the feeding cables, make holes in the
marked locations underneath on the base and fit suitable grommets or cable glands.
Connecting the sensors
Cables with a minimum cross-section of 2 x 0.5 mm² can be connected to the terminals at
the controller base unit.
Electrical connection
39
EB 5432 EN