Parameter List - Samson TROVIS 5432 Mounting And Operating Instructions

Automation system 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5432:
Table of Contents

Advertisement

Appendix

12.2 Parameter list

P
Designation
P1
Gradient
P2
Level
P3
Min. flow temperature
P4
Max. flow temperature
P5
Max. return flow
temperature
P6
Monitoring value for priority
P7
Delay
P8
K
Return flow temperature
P
limit
P9
Set-back of flow tempera-
ture in reduced operation
P10 K
Three-step control
P
P11 T
Three-step control
N
P12 T
Three-step control
Y
P13 On/off differential
P14 Min. activation time for
on/off control
P15 Min. deactivation time for
on/off control
P16 DHW set point
P17 Advance heating time
P18 Cycle rate
P Parameter, WE Default setting
42
EB 5432 EN
WE
Range of value
1.6
0.2 to 3.2
0 °C
–30 to 30 °C
30 °C
0 to 130 °C
80 °C
0 to 130 °C
20 to 90 °C
50 °C
40 °C
20 to 90 °C
3 °C/h
1 to 6 °C/h
0.1 to 50.0
1.0
0 to 50 °C
15 °C
2.0
0.1 to 50.0
120 s
0 to 999 s
45 s
10 to 240 s
2 to 10 °C
5 °C
0 to 600 s
120 s
0 to 600 s
120 s
45 °C
20 to 90 °C
120 min
0 to 360 min
0 min
0
to 100 min/
and
1
to 100 min
10 min

Advertisement