Appendix
12.5 User data
Station
Operator
Responsible SAMSON office
Function blocks
F1
F2
Parameters
P
Designation
P1
Gradient
P2
Level
P3
Min. flow temperature
P4
Max. flow temperature
P5
Max. return flow temperature
P6
Monitoring value for priority
P7
Delay
P8
K
Return flow temperature limit
P
P9
Set-back of flow temperature in reduced
operation
P10
K
Three-step control
P
P11
T
Three-step control
N
P12
T
Three-step control
Y
P13
On/off differential
P14
Minimum activation time for on/off control
P15
Minimum deactivation time for on/off control
P16
DHW set point
P17
Advance heating time
P18
Cycle rate
44
EB 5432 EN
F3
F4
F5
F6
Setting
F7
F8
Range of values
0.2 to 3.2
–30 to 30 °C
0 to 130 °C
0 to 130 °C
20 to 90 °C
20 to 90 °C
1 to 6 °C
0.1 to 50
0 to 50 °C
0.1 to 50
0 to 999 s
10 to 240 s
2 to 10 °C
0 to 600 s
0 to 600 s
20 to 90 °C
0 to 360 min
0
to 100 min/
1
to 100 min
F9