Party mode (constant rated operation)

1.8
Function independent of controller setting.
The party mode function sets the controller in rated operation mode: regardless of the pro-
grammed times-of-use, the Set point day or Flow temperature set point are constantly used
by the controller.
The party mode function is set in the operating level (set point display).
Proceed as follows:
Note!
The controller is in constant rated operation when PArtY appears on the display. The controller
exits the constant rated operation mode when the current set point is reset (–> section 1.9).
3s Switch to user level.
Display: Time.
q
Select OT deactivating value in rated operation or
OT deactivating value in reduced operation .
Open data point.
q
Change data point.
Confirm data point.
q
Select End on the display.
Switch to operating level.
q
Select menu PArtY (turn knob to the right as far as it
will go). The display blinks.
Confirm party mode. Alternatively:
Wait 3 minutes until the display stops blinking.
The party mode is activated.
Operation
13
EB 5432 EN