Functions of the heating circuit
Examples for setting the characteristic:
4
Old building, radiator design 90/70:
4
New building, radiator design 70/55:
4
New building, radiator design 55/45:
4
Underfloor heating depending on arrangement: Gradient smaller 0.5
Weather-compensated control, room set point mode
Functions
Type of control
Room set point mode
Parameter
Day set point
Night set point
Gradient
Level
Min. flow temperature
Max. flow temperature
Weather-compensated control
Functions
Type of control
Room set point mode
Parameter
OT deactivating value in rated operation
OT deactivating value in reduced operation
Gradient
Level
Min. flow temperature
Max. flow temperature
Set-back of flow temperature in reduced operation
24
EB 5432 EN
Gradient approx. 1.8
Gradient approx. 1.4
Gradient approx. 1.0
WE
Configuration
1
F1 - 1
1
F9 - 1
WE
Level / Range of values
20 °C
User level / 10 to 40 °C
15 °C
User level / 10 to 40 °C
1.6
CoPa level P1 / 0.2 to 3.2
0 °C
CoPa level P2 / –30 to 30 °C
30 °C
CoPa level P3 / 0 to 130 °C
80 °C
CoPa level P4 / 0 to 130 °C
WE
Configuration
1
F1 - 1
1
F9 - 0
WE
Level / Range of values
22 °C
User level / 0 to 50 °C
15 °C
User level / –30 to 50 °C
1.6
CoPa level P1 / 0.2 to 3.2
0 °C
CoPa level P2 / –30 to 30 °C
30 °C
CoPa level P3 / 0 to 130 °C
80 °C
CoPa level P4 / 0 to 130 °C
15 °C
CoPa level P9 / 0 to 50 °C