Manual operation mode

3
Manual operation mode
In manual operation mode, the circulation pump UP is always switched on. The output SLP is
usually switched off. Initially, no control signal is issued for the heating circuit.
Activate the manual operation mode in the configuration and parameterization level (CoPa
level) over function block F2.
Functions
Manual operation of an actuator
Proceed as follows:
3s Switch to user level.
Display: Time
q
Select End on the display.
3s Switch to the configuration and parameterization level (CoPa level).
Display: 0, nr blinks.
q
Set key number.
Confirm key number.
Display: F1
q
Select function block F2.
Open function block F2.
q
Activate function block F2.
Display: F2 - 1.
Activate manual operation mode.
Display:
q
Move the actuator manually:
oPEn: OPEN (3-step signal); activate output (on/off signal)
StoP: Last position (3-step signal); deactivate output (on/off signal)
cLoSE: CLOSED (3-step signal)
Note!
The frost protection function is not active in manual operation mode.
16
EB 5432 EN
and StoP
WE
Configuration
0
F2 - 1