Appendix; Function Block List - Samson TROVIS 5432 Mounting And Operating Instructions

Automation system 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5432:
Table of Contents

Advertisement

12

Appendix

12.1 Function block list

F
Function
F1
Type of control
F2
Manual operation of
actuator
F3
Delayed adaptation to
outdoor temperature
F4
Control signal
F5
Summer time/winter time
changeover
F6
Drying of jointless floors
F7
Room panel
F8
On/off differential of
storage tank charging
F9
Room set point mode
F Function block, WE default setting
WE
Comments
1
F1 - 1: Weather-compensated control
F1 - 0: Fixed set point control or
F1 - 0 and F7 - 1: Room temperature-based control
0
F2 - 1: Manual operation mode active
0
F3 - 1: Delayed adaptation to outdoor temperature,
only effective with F1 - 1
1
F4 - 1: 3-step control
F4 - 0: On/off control
1
F5 - 1: Changeover active
0
F6 - 1: Drying of jointless floors active
After the function's running time has elapsed, F6 - 0 is set.
0
F7 - 1: Connection of Type 5257-5 Room Panel to S4/S5
F7 - 0: DHW priority, storage tank charging over S4/S5
(depending on circuit)
0
F8 - 1: On/off differential = 2 °C
F8 - 0: On/off differential = 5 °C
1
Only effective with F1 - 1:
F9 - 1: Room set point assignable
F9 - 0: Set-back and outdoor temperature dependent
deactivating values assignable
Appendix
41
EB 5432 EN