Correcting The Set Point; Correcting The Set Point Temporarily; Correcting The Set Point Permanently - Samson TROVIS 5432 Mounting And Operating Instructions

Automation system 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5432:
Table of Contents

Advertisement

Operation
1.9

Correcting the set point

The current set point is displayed in the operating level. In rated operation, the Day set point
or the Flow temperature set point appears on the display (–> section 1.3). In reduced opera-
tion, the Night set point or the Reduced flow temperature set point appears on the display.

1.9.1 Correcting the set point temporarily

The current set point which appears on the display can be changed for just as long as the
rated operation mode (programmed time-of-use period) is running or the reduced operation
mode (outside of the time-of-use period) is running.
This temporary correction of the set point is made in the operating level (set point display).
Proceed as follows:
q
Turn the control knob one position.
The icon display blinks.
q
Change the parameter.
Confirm the new parameter setting. Alternatively:
Wait until the display stops blinking.
The new parameter setting has been saved.
The temporarily active set point (corrected once) is indicated on the display by the
icon together with the

1.9.2 Correcting the set point permanently

The permanent change of Day set point or Flow temperature set point in rated operation as
well as the Night set point or Reduced flow temperature set point in reduced operation is
made in the user level.
Proceed as follows:
3s Switch to user level. Display: Time
q
Select menu Set point (–> page 6).
Open the set point.
q
Change the set point.
Confirm the set point.
q
Select End on the display.
Switch to operating level.
14
EB 5432 EN
icon.