Start-up

2.1

Configuration and parameterization

The controller is configured and parameterized in the configuration and parameterization
level (–> Fig. 10 on page 49). After accessing the configuration and parameterization level
(CoPa level), the function blocks F1 to F9 appear at first, followed by the parameters P1 to
P18. The individual functions and parameters are listed in the Appendix (–> page 41).
The configuration and parameterization level is locked to prevent unintentional and unautho-
rized access. This level can only be opened when the key number is known. The key number
can be found on page 48. To avoid unauthorized use of the key number, remove the page
or make the key number unreadable.
Proceed as follows:
3s Switch to user level. Display: Time
q
Select End on the display.
3s Switch to the configuration and parameterization level (CoPa level).
Display: 0, nr blinks.
q
Set key number.
Confirm key number. Display: F1
q
Select function block* or parameter.
Open selected data point.
q
Change data point.
Confirm setting of the data point.
To set further function blocks and parameters, repeat the instructions in the fields highlighted
in gray.
q
Select End on the display.
Return to operating level.
Display: Current set point
* Note!
A function block is activated when F_ 1 appears on the display; it is deactivated when F_ 0
appears on the display.
Start-up
15
EB 5432 EN