flow temperature of 20 °C, provided the temperature still lies below the Monitoring value for
priority.
Three different operating conditions exist:
4
The DHW temperature at S4 (S5/S2) is under the Monitoring value for priority –> the
heating circuit set point is reduced.
4
The DHW temperature to S4 (S5/S2) is up to 5 °C above the Monitoring value for prior-
ity –> the heating circuit set point remains unchanged.
4
The DHW temperature to S4 (S5/S2) exceeds the Monitoring value for priority by more
than 5 °C –> the heating circuit set point which was reduced due to the priority is in-
creased.
Functions
Room panel
* F7 - 0:
Monitoring value for priority at S4 (depending on the circuit) or storage tank
charging and
Monitoring value for priority at S5
F7 - 1:
Storage tank charging and monitoring value for priority at S2 (room
temperature-based control)
Parameter
Monitoring value for priority
WE
Configuration
0
F7 *
WE
Level / Range of values
40 °C
CoPa level P6 / 20 to 90 °C
Functions of the DHW circuit
EB 5432 EN
31