Section 5
Bay protection functions
5.11.4

Function settings

Table 93: Logic function - settings
Text
ParSet 4..1
Logic Mode
BinOutput
BlockInp
BinInp1 (R1)
BinInp2 (R2)
BinInp3 (S1)
BinInp4 (S2)
5.11.5

Parameters

Table 94: Logic function - parameters
Signal
ParSet 4..1
Logic Mode
BinOutput
BlockInp
BinInp (R1)
BinInp2 (R2)
BinInp3 (S1)
BinInp4 (S2)
5.12

Delay/Integrator (DELAY)

5.12.1

Mode of operation

General purpose timer for:
174
Unit
Default
P1
OR
SignalAddr
BinaryAddr
Always off
BinaryAddr
Always off
BinaryAddr
Always off
BinaryAddr
Always off
BinaryAddr
Always off
Description
Parameter for determining in which set of parameters a particular function is active.
Definition of the logic function to be performed by the 4 binary inputs. Possible
settings:
OR: OR gate with all 4 binary inputs
AND: AND gate with all 4 binary inputs
R/S flip-flop: Flip-flop with 2 set inputs (S1 and S2) and 2 reset inputs (R1 and
R2). The output is set or reset when at least one of the corresponding inputs is
at logical
1 (OR gate). Reset inputs take priority over the set inputs.
Output for signaling a trip (logic) respectively tripping (trip logic)
Input for blocking the function
F: not used
xx: all binary inputs (or outputs of protection functions)
The output is always at logical
input acts as a reset input for the flip-flop function.
Binary inputs 1 to 4 (AND or OR function)
Reset inputs 1 and 2 and set inputs 1 and 2 (RS flip-flop)
F: not used (OR logic or RS flip-flop in logic mode)
T: not used (AND logic in logic mode)
xx: all binary inputs (or outputs of protection functions)
© Copyright 2019 ABB. All rights reserved
GUID-A7084910-3F39-4F82-994C-CB19D2C42F70 v1
Min
Max
(Select)
(Select)
GUID-FFD23A75-A981-4847-AA5D-AA085E47A10A v1
0 when the blocking input is at logical 1 . The blocking
GUID-B9A42598-E62D-4AAC-8FE6-8C1DA244A48C v1
Bay protection functions REB500