Power swing blocking
The purpose of the power swing blocking function is to prevent unwanted tripping of the
distance protection function in response to power system instability with oscillatory
fluctuations of power (power swings) or loss of synchronism (out-of-step). The power swing
blocking function does not influence the operation of the back-up overcurrent function.
When power swings occur, the electrical parameters of the system vary at a slower or faster
rate in relation to the angle δ be-tween the voltage vectors of the energy sources in different
parts of the system. In the case of a fault on the other hand, step changes of these parameters
take place. The parameters, which regardless of location are subject to appreciable variation in
the general region around phase opposition (δ = 180°), are the resistance R and the voltage
component U × cosϕ. The value of ϕ corresponds to the angle between phase voltage and
current.
Bay protection functions REB500
Technical manual
Signals TRIP 4
In
X
X
X
X
© Copyright 2019 ABB. All rights reserved
Out
Source
Binary output: TRIP CB L1
Binary output: TRIP CB L2
Binary output: TRIP CB L3
TRIP3
X
Binary output: Trip Com Rec
X
Binary output: TRIP L1L2L3
X
Binary output: Trip CB 3PH
X
Binary output: Trip CB 1PH
Section 5
Bay protection functions
Drain
GUID-E4D40E54-C506-4C96-B702-3FF8969E6661 v1
89

Advertisement

Table of Contents
loading

Table of Contents