Measurement - ABB RELION REB500 Technical Manual

Bay protection functions
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 406-UEN B
Phase preference logic
The desired phase preference logic for cross-country faults is chosen with the aid of the
parameter
In solidly grounded systems, the
ground or Forward OR .
It is essential for all the relays in ungrounded systems and systems with Petersen coils to be
set to the same phase preference logic. The logic used in the system must be known before
one of the eight alternative schemes can be selected:
L1L3L2(L1) — cyclic
L3L1L2(L3) — cyclic
L1L3L2 — acyclic
L1L2L3 — acyclic
L3L2L1 — acyclic
L3L1L2 — acyclic
L2L1L3 — acyclic
L2L3L1 — acyclic
Undervoltage starters (Uweak)
The undervoltage starters are used in conjunction with the switch-onto-fault function and the
transfer tripping schemes (POTT and PUTT NONDIR). The corresponding pick-up value is set in
relation to the rated voltage with the aid of the parameter
0 to 2 U
5.1.6.3

Measurement

All the settings for the impedance measuring zones are to be found in the Measurement sub-
menu.
Determining the distance zones
Before it is possible to determine the reaches of the distance zones, the impedances and
phase-angles of the line sections during faults must be known. Typical settings for the various
zone reaches along the line are given below:
A
IEC19000408 V1 EN-US
Figure 7:
Bay protection functions REB500
Technical manual
Should it not be possible to find a setting, which satisfies both these
conditions, the neutral voltage (
addition to the neutral current.
PhaseSelMode .
in steps of 0.01.
N
Z = 0.85 (a + k · b )
3
Z = 0.85 (a + k · b )
2
Z = 0.85 · a
1
Z
= 1.2 · a
ÜR
a
Typical settings for the reaches of distance relay zones
© Copyright 2019 ABB. All rights reserved
3U0min ) must be used for measurement in
PhaseSelMode parameter is disabled by setting it to Solid
2
1
b
b
B
Bay protection functions
GUID-C3BD8775-B46E-437E-B3B9-F082CFAB583E v1
GUID-2E537DE1-4FD1-476E-A15F-3F0354C6C425 v1
Uweak , which has a setting range of
GUID-1C206723-EE56-4815-829C-56FD2084967D v1
GUID-05267329-6581-44F6-A236-96D275BADFAC v1
b
2
1
C
18000006-IEC19000408-1-en.vsdx
Section 5
41