Main protection 1 not ready
Trip CB
Trip CB 3P
Start
Def. Trip
Close CB
ZExtension
First AR 1P
Trip 3- Pol
AR in Prog.
AR Ready
AR Blocked
Trip CB
Trip CB 3P
Start
Def. Trip
Close CB
ZExtension
First AR 1P
Trip 3- Pol
AR in Prog.
AR Ready
AR Blocked
IEC19000463 V1 EN-US
Figure 59: Timing diagram for scheme with main protections 1 and 2 (REB500sys), both
Settings:
1. AR Mode = 1P-1P or 1P3P-1P3P,
2..4. AR Mode = off
Zextension = on
ZE 1. AR = off
5.8.8

Checking the dead times

When commissioning the autoreclosure function, it is not sufficient to check the combined
operation of protection function, autoreclosure function and circuit-breaker, the resulting
dead times must also be determined.
154
Main protection 2, AR active
time < t Oper.
t Discrim. 1P
t Dead1 1P
equipped with an autoreclosure function — Main protection 1 not in operation
>> Response for unsuccessful autoreclosure
© Copyright 2019 ABB. All rights reserved
(
because main protection 1 not ready)
18000058-IEC19000463-1-en.vsdx
1MRK 505 406-UEN B
GUID-AB1C349F-B540-4E71-B77D-D3DA75A571CE v1
Bay protection functions REB500
Technical manual