Section 3
Configuring bay protection using HMI500
3.4.3
3.4.4
3.5
32
Recording a binary signal as an event
Only bay protection binary signals can be configured to be recorded as events that
are also configured via menu "Configuration/ Binary module" (output signals do
not necessarily have to be assigned to output relays).
Disturbance recording of a binary signal
Binary output signals generated by bay protection functions can be configured for
disturbance recording, providing they are configured in the "General purpose" dia-
log for the binary output function (see Figure 18).
Binary input signals of the bay protection functions can be configured for disturb-
ance recording, providing they are configured in the "General purpose" dialog for
the binary input function (see Figure 14) and also as a binary input via the HMI500
menu "Configuration/Binary module/Inputs" menu.
Protection function settings
The appropriate dialog for setting a protection function is opened by double click-
ing the left mouse button on the respective symbol or via the context menu.
Figure 19
Protection function settings
The settings in the dialog for each protection function are described in detail in
Section 5.
1MRK 505 353-UEN
Application Manual
Bay protection functions REB500