Parameters - ABB RELION REB500 Technical Manual

Bay protection functions
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

Section 5
Bay protection functions
5.1.5

Parameters

Table 42: General
Parameter
ParSet 1..4
CT Neutral
Ref. Length
U input
I input
I
input,
0
I
input
0P
I O/C backup
Delay O/C backup
Time PS block
Table 43: Starting
Text
StartMode
PhaseSelMode
GndFaultMode
Table continues on next page
30
Description
Parameter for determining in which set of parameters a particular function is active.
Side of the CTs on which the star-point is formed (current direction).
Choice:
Bus side
Line side
Reactance (secondary value) to be used as reference length of the line.
Indicates the first VT input assigned to the three-phase voltages. Fixed setting
Channel 5 of the A/D module.
Indicates the first CT input assigned to the three-phase currents. Fixed setting
Channel 1 of the A/D module.
Indicates the CT input assigned to the neutral current. This is used for
the external acquisition of the neutral current of the line or
the neutral current of the parallel circuit of a double-circuit line. Fixed setting
Channel 4 of the analogue input module.
Phase current pick-up setting of the backup overcurrent unit. The function is
blocked when set to zero.
Tripping delay of the O/C backup function.
Determines the maximum blocking time of the power swing blocking function. The
power swing blocking function is blocked when set to zero.
Explanation
Choice:
UZ (underimpedance)
I > (overcurrent)
Phase preference for cross-country faults in systems with Petersen coils and
ungrounded systems:
Choice:
Solidly grounded
L1L3L2 (L1) cyclic
L3L1L2 (L3) cyclic
L1L3L2 acyclic
L1L2L3 acyclic
L3L2L1 acyclic
L3L1L2 acyclic
L2L1L3 acyclic
L2L3L1 acyclic
Directional OR
Method of detecting ground faults:
Choice:
I
: (I
>3I
) AND (I
0
E
0min
I
OR U
: (I
>3I
0
0
E
0min
I
(I
): (I
>3I
) AND (I
0
2
E
0min
I
(I
) OR U
: (I
>3I
0
2
0
E
© Copyright 2019 ABB. All rights reserved
>0.25 I
)
E
max
) AND (I
>0.25 I
) OR (U
>3U
E
max
E
>0.23 I
)
E
2
) AND (I
>0.23 I
) OR (U
0min
E
2
E
Bay protection functions REB500
1MRK 505 406-UEN B
GUID-94E19491-6E52-44C9-813E-33C133EF4CC3 v1
)
0min
>3U
)
0min
Technical manual