ABB RELION REB500 Technical Manual page 65

Bay protection functions
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 406-UEN B
Z
R
where,
k
: zero-sequence compensation factor for Z
0
k
0m
line
The mutual zero-sequence impedance of a double-circuit line (k
for the first, second and overreaching zones, and in the latter two cases, only if their direction
of measurement is the same as that of the first zone. In this respect, a reverse measuring zone
is treated in the same manner as an overreaching zone.
The mutual zero-sequence impedance (k
I
or the direction of I
E
from being adversely influenced by a fault relatively close to the relay location of the faulted
circuit.
Assuming a fault between L1 and L2, the impedance of the phase-to-phase loop is calculated
using the equation:
Z
L L
1 2
It is determined almost simultaneously, whether the impedance measured lies within the
characteristic and whether it is in the direction of the first zone and overreaching zone, or in
the direction of the reverse measuring zone. The corresponding tripping and other signals are
processed by the system logic. Tripping of the circuit-breaker, however, only takes place after
a measuring unit has operated twice.
Bay protection functions REB500
Technical manual
U
L
1
  
I
k I
k
I
L
1
0
E
0
m
Em
  
k
/ 3
Z
0
1
: zero-sequence compensation factor for the mutual impedance Z0m of double-circuit
k
Z
3
Z
0
m
0
m
1
not be the same as that of I
Em
U
U
L
1
L
2
I
I
L
1
L
2
© Copyright 2019 ABB. All rights reserved
(compensated)
0
× I
) is not compensated, should I
0m
Em
. This prevents a healthy parallel circuit
E
Bay protection functions
× I
) is only compensated
0m
Em
exceed 1.25 ×
Em
Section 5
59

Advertisement